2" CDF® Fuel Monitor Cartridges for Aviation Fuel Filtration

CDF Fuel Monitor Cartridge

Field Proven: CDF® Fuel Monitor Cartridges

Assure Clean Dry Fuel Delivery

Absorb water and filter solids from Avgas and jet fuel.

Provide protection against water slug transmission.

2" CDF® Fuel Monitor Cartridges

BENEFITS

  • CDF® P SERIES are qualified to EI 1583 7th Edition specification for Aviation Fuel Filter Monitors.
  • IMPROVED SALT WATER PERFORMANCE
  • IMPROVED WATER CAPACITY
  • IMPROVED WATER REMOVAL EFFICIENCY
  • CONDUCTIVE END CAPS, O-rings, and adhesive reduce static charge within the vessel.
  • O-RING SEAL minimizes the possibility of bypassing contaminated fuel at differential pressures up to 175 psi.
  • RUGGED CONSTRUCTION collapse strength exceeds 175 psi differential pressure.
  • CENTER TUBE provides enhanced structural integrity and additional conductivity as further static charge protection

DESCRIPTION

The Parker Velcon CDF® P Series cartridges provide superior performance and reliability in standard fuel monitor housings through a unique, combination of media that absorbs water and filters solids that might be present in the fuel while helping reduce static charge build-up inside the vessel.

The injection molded endcaps bond with the media and with the O-ring seal on the outlet end. This minimizes the possibility of bypassing contaminated fuel or transmission of water downstream at low flow rates.

As the cartridge removes water and/or contaminant from the influent fuel the pressure differential will increase along with a decrease in flow rate. These changes are the result of flow restriction caused by dirt retention or water absorption in the media. The rate of these changes depends on the quantity of water or contamination in the fuel.

*****CAUTION*****
DO NOT USE WITH PRE-MIXED FUELS CONTAINING
ANTI-ICING ADDITIVES

CDF Fuel Monitor Cartridge Cutaway

EI 1583 7th Edition Information

Parker Velcon CDF® P Series Cartridges incorporate several structural features designed to meet the requirements of EI 1583 7th Edition including:

  • Increased product conductivity to decrease the risk of electrostatic discharges
  • Improved media structure to lower the risk of media migration
  • Lower initial DP - a major factor for installations that require changing cartridges at 15 PSID
  • New structure that provides longer cartridge life in the presence of small amounts of water

Some of the requirements of the 7th edition of EI 1583 are:

  • Salt resistance tests
  • Water slug test at low flow (10% of rated flow)
  • Tests for trace SAP migration
  • Structural integrity test
  • Low water (50 ppmv) at low flow (10% of rated flow)
  • Testing for cartridge conductivity

CARTRIDGE SELECTION TABLE

Cartridge Flow Rate (USGPM)

Velcon Model Number Overall Length (in.) Replacements for:
Facet Model# Faudi Model #
5 CDF-205P 5-13/16 FG-205-7 M.2-134/6B
10 CDF-210P 10-13/16 FG-210-7 M.2-261/6B
15 CDF-215P 15-13/16 FG-215-7 M.2-387/6B
20 CDF-220P 20-13/16 FG-220-7 M.2-515/6B
25 CDF-225P 25-13/16 FG-225-7 M.2-642/6B
30 CDF-230P 30-13/16 FG-230-7 M.2-770/6B

All cartridges are packaged 20 per carton

SPECIFICATIONS AND TECHNICAL INFORMATION CDF® P SERIES

  • Collapse strength: 175 psid (12 bar)
  • Rating: 0.5 micron
  • Maximum Operating Temperature: 160°F (71.1°C)
  • Recommended changeout differential pressure = 15 psid (1 bar)
  • Typical water holding capacity for CDF-230P is 200 ml.
  • For service life information, please refer to Operating Procedures VEL1839 or consult your company fuel handling procedures.