On-Line Oil Filtration
for Load Tap Changer Compartments

The TP3 was developed in response to the utility industry’s desire to reduce operation and maintenance costs and increase system reliability. On-line oil filtration has proven to be an effective means of combating LTC problems. Tap changers retrofitted with a TP3 enjoy the following:
- Consistent high oil dielectric strength
- Extended maintenance/inspection intervals
- Reduced contact wear and coking
- Extended oil life
- Reduced contact erosion via reduced restrikes during tap changing
The Velcon TP3 is recommended for installation on tap changers that:
- Perform a high number of operations
- Exhibit consistent sludging conditions
- Have a high tap-to-tap voltage difference
- Require frequent attention
Quality components and comprehensive design features have made the TP3 an industry standard for on-line filtration. All components are fully enclosed in a NEMA 4 cabinet. Operation of the unit is unattended (and controlled by a mechanical timer). A flow rate of 3 gpm keeps turbulence in the reservoir to a minimum and allows for maximum filter life.
FEATURES
Automatic Shut-Off
Pressure switch turns the system off when filter is plugged. Relay can be wired to remote alarm or indicator light.
Oil Make-Up
LTC reservoir can be topped off using 3-way valve oil make-up port.
Hour Meter
Records run time of system to assure user of consistent operation.
Timer
24-hour mechanical timer can be set for hours of daily operation.
SPECIFICATIONS
Mechanical
Flow Rate:
3 gallons per minute
Cabinet:
NEMA 4 enclosure, painted grey acrylic, easy-opening handle with lock and 3-point latch, with louvers and filters, UL/CSA approved. Dimensions are: 43” x 30” x 12” (H-W-D)
Pump:
Heavy-duty, self-priming, positive displacement gear pump with built-in pressure relief valve and mechanical seal.
Piping:
Stainless steel tubing, JIC hydraulic fittings. External connections are 1/2” female NPT.
Filter Vessel:
Velcon Model VF-71E, with manual vent and static pressure gauge, is epoxy coated internally and externally. No tools required for filter changeout.
Filter:
Velcon Model FO-718PL1/2 comes installed for removal of carbon contamination.
Sight Glass:
150 psi maximum working pressure for oil flow indication.
Electrical
Motor:
1/2 hp, 120V, 1-phase, 1740 rpm, TEFC
Control box:
NEMA 12 with high pressure switch, latching relay, magnetic contactor, hour meter, and manual starter/disconnect with 10 amp heater overload
Wiring:
16 ga., XLPE grade, all terminal connections
Power requirements:
120 vac, single-phase, 10 amps
ORDERING INFORMATION
Specify model number as shown below. Units are shipped with cartridge installed.
System Part Number: TP3-1 (120V, 1ph, 60Hz)
Also Available: 3-phase power, 50 Hz power (contact factory)
Weight: 250 pounds
Shipping Weight: 325 pounds
Crated Dimensions: 47” x 34” x 21”
OPTIONS & ACCESSORIES
| 643Y051 |
Door Mounted View Window |
| 241X051 |
3/4” JIC Port Connections (2 ea required) |
| 723Y005 |
No-Flow Shut-Off Switch |
| 552Y025 |
Stainless Steel Valve Upgrade |
| 605Y020 |
Timed Run Via Remote Start Signal From Tap Changer |
| 031Y104 |
0.5 micron AC-7181/2 Cartridge
for particle and free water removal |
| 031Y105 |
0.3 micron AC-718P3 Cartridge
for particle and free water removal |
| 031Y106 |
0.3 micron FO-718PLP3 Cartridge
for particle removal |
| 031Y102 |
0.3 micron SD-718P3 Superdri® Cartridge
for particle and dissolved water removal |
RECOMMENDED SPARES
| FO-718PL1/2 |
Filter Cartridge, box of 6 ea (or:) |
| FO-718PLP3 |
Filter Cartridge, box of 6 ea (or:) |
| AC-7181/2 |
Aquacon® Cartridge, box of 6 ea (or:) |
| AC-718P3 |
Aquacon® Cartridge, box of 6 ea (or:) |
| SD-718P3 |
Superdri® Cartridge, box of 6 ea |
| G-1016 |
Filter Housing Lid Gasket, 1 ea |
Tap Changer Filter System TP# - Data Sheet #1775 |